Inverter Sizing Calculator
Size an inverter for an off-grid home, RV, boat, or backup system. Accounts for diversity factor (not all loads run at once) and motor starting surge (3× continuous for ~100 ms on induction motors).
Your AC loads
| Load | Watts | Qty | Motor? | |
|---|---|---|---|---|
Recommendation
Summed AC nameplate is 2,750 W. At a 70% diversity factor, continuous is 1,925 W. Adding 25% headroom yields 2,406 W continuous. The Fridge (modern) motor adds a 200% starting surge (450 W for ~100 ms). Inverter peak efficiency assumed 93%. Rounded up to a standard 3,000 W inverter. On the DC side at 48V, that draws 67.2 A continuous (53.2 A on surge) — size battery cables and the inverter OCPD against this continuous-amp figure with the 25% headroom + 1.25× cable-ampacity multiplier baked into your wire calc.
Design the full system →Why rounding up matters
Inverter manufacturers rate continuous power at 25 °C. In a sealed battery compartment at 40 °C, the same inverter de-rates to about 80% of nameplate. A 3 kW inverter run at 2.9 kW continuous in summer is a ticket to premature failure. Add 25% headroom minimum; more if it lives somewhere hot.
Motor surge is the silent killer
A 1 HP (746 W) well pump pulls ~2.2 kW for 50–150 ms when it starts. Adding it to a 2 kW inverter running 1.5 kW continuous trips the surge protection. The calculator above accounts for the largest single motor — but if you have two motors that might start within the same 100 ms window (rare, but happens with bad pump-controller logic), size for both surges.
120V vs 120/240V split-phase
If your home has any 240 V appliance (well pump, some dryers, electric water heaters, AC condensers), you need a split-phase inverter or a pair of inverters stacked in series. Split-phase units cost roughly 30% more but eliminate the hack of rewiring 240 V loads to run on 120 V legs.
Want this inverter sized against your actual loads, battery bank, and solar array — with a permit-ready PDF? Design the full system.
Code references
The Inverter Sizing math above sits inside a regulatory framework. Inspectors and underwriters look at the citations below — your installation has to satisfy them, not just produce a number that looks reasonable.
- NEMA AB-1 (2014, R2024)Molded-case circuit breakers feeding inverter loads must coordinate with the inverter's peak-surge waveform. The standard quantifies thermal-magnetic trip envelopes; inverters with brief 3× surges typically need a magnetic trip ≥150% of continuous rated current to avoid nuisance trips during motor start.Why it matters: The 3× motor-surge factor this calculator applies is the same envelope NEMA AB-1 uses to size upstream OCPDs. Pulling continuous + surge from the same model keeps your breaker and inverter selections consistent.
- NEC 690.8(A)(3) (2023 / 2026)Maximum AC output current of an interactive inverter equals the inverter's continuous output current at nominal AC voltage. DC battery-cable ampacity must be sized at 1.25× this current, then again at 1.25× per 690.8(B) for continuous-duty conductors.Why it matters: The DC bus continuous-amp output of this calculator already includes the 25% headroom; multiply by 1.25 again when sizing battery cables for continuous-duty AC inverters per NEC.
- ABYC E-11 §11.10.1 (2018) / Supplement 65 (2025)Each ungrounded conductor must be protected by an overcurrent device sized to ≤150% of the conductor ampacity. The 2025 Supplement 65 adds §11.5.1.4: battery banks >500 Ah at 12 V (or proportional energy at higher voltages) require a per-battery OCPD with sufficient AIC.Why it matters: For marine inverter installs, the DC bus continuous current this calculator emits is the input to the OCPD sizing rule — not the AC continuous rating. Banks larger than 500 Ah additionally need per-battery protection under E-11 (2025).
- IEEE 1547-2018Grid-interactive inverters (when used in hybrid systems with utility tie-in) must respond to anti-islanding, voltage and frequency ride-through within bounds defined per Category I/II/III response.Why it matters: Stand-alone inverter sizing (this tool) does not require IEEE 1547 compliance; if your design becomes grid-interactive, the inverter SKU you pick must carry an IEEE 1547-2018 certification on its nameplate.
Citations are paraphrased for brevity. Always work from the most recent published edition of each standard for permit submittals.