Inverter Sizing Calculator

Size an inverter for an off-grid home, RV, boat, or backup system. Accounts for diversity factor (not all loads run at once) and motor starting surge (3× continuous for ~100 ms on induction motors).

Your AC loads

LoadWattsQtyMotor?
Nameplate total: 2,750 W across 5 loads

Recommendation

Recommended continuous rating
3,000 W
Continuous (at diversity)
1,925 W
Required (+25% headroom)
2,406 W
Peak surge
2,375 W
Largest motor
Fridge (modern) (450 W surge)
DC bus current — continuous (48V)
67.2 A
DC bus current — surge (48V)
53.2 A
Recommended W ÷ 48 V ÷ 93% inverter efficiency. Size battery cables + the inverter input OCPD against the continuous-amp figure with a 1.25× ampacity multiplier.

Summed AC nameplate is 2,750 W. At a 70% diversity factor, continuous is 1,925 W. Adding 25% headroom yields 2,406 W continuous. The Fridge (modern) motor adds a 200% starting surge (450 W for ~100 ms). Inverter peak efficiency assumed 93%. Rounded up to a standard 3,000 W inverter. On the DC side at 48V, that draws 67.2 A continuous (53.2 A on surge) — size battery cables and the inverter OCPD against this continuous-amp figure with the 25% headroom + 1.25× cable-ampacity multiplier baked into your wire calc.

Design the full system →

Email me a copy of this inverter sizing result

We'll send a clean snapshot to your inbox so you can save, print, or forward to your installer. No account needed.

By submitting your email you agree to receive your design snapshot and occasional product updates from MarinePowerLab. Unsubscribe in any email.

Why rounding up matters

Inverter manufacturers rate continuous power at 25 °C. In a sealed battery compartment at 40 °C, the same inverter de-rates to about 80% of nameplate. A 3 kW inverter run at 2.9 kW continuous in summer is a ticket to premature failure. Add 25% headroom minimum; more if it lives somewhere hot.

Motor surge is the silent killer

A 1 HP (746 W) well pump pulls ~2.2 kW for 50–150 ms when it starts. Adding it to a 2 kW inverter running 1.5 kW continuous trips the surge protection. The calculator above accounts for the largest single motor — but if you have two motors that might start within the same 100 ms window (rare, but happens with bad pump-controller logic), size for both surges.

120V vs 120/240V split-phase

If your home has any 240 V appliance (well pump, some dryers, electric water heaters, AC condensers), you need a split-phase inverter or a pair of inverters stacked in series. Split-phase units cost roughly 30% more but eliminate the hack of rewiring 240 V loads to run on 120 V legs.

Want this inverter sized against your actual loads, battery bank, and solar array — with a permit-ready PDF? Design the full system.

Code references

The Inverter Sizing math above sits inside a regulatory framework. Inspectors and underwriters look at the citations below — your installation has to satisfy them, not just produce a number that looks reasonable.

  • NEMA AB-1 (2014, R2024)
    Molded-case circuit breakers feeding inverter loads must coordinate with the inverter's peak-surge waveform. The standard quantifies thermal-magnetic trip envelopes; inverters with brief 3× surges typically need a magnetic trip ≥150% of continuous rated current to avoid nuisance trips during motor start.
    Why it matters: The 3× motor-surge factor this calculator applies is the same envelope NEMA AB-1 uses to size upstream OCPDs. Pulling continuous + surge from the same model keeps your breaker and inverter selections consistent.
  • NEC 690.8(A)(3) (2023 / 2026)
    Maximum AC output current of an interactive inverter equals the inverter's continuous output current at nominal AC voltage. DC battery-cable ampacity must be sized at 1.25× this current, then again at 1.25× per 690.8(B) for continuous-duty conductors.
    Why it matters: The DC bus continuous-amp output of this calculator already includes the 25% headroom; multiply by 1.25 again when sizing battery cables for continuous-duty AC inverters per NEC.
  • ABYC E-11 §11.10.1 (2018) / Supplement 65 (2025)
    Each ungrounded conductor must be protected by an overcurrent device sized to ≤150% of the conductor ampacity. The 2025 Supplement 65 adds §11.5.1.4: battery banks >500 Ah at 12 V (or proportional energy at higher voltages) require a per-battery OCPD with sufficient AIC.
    Why it matters: For marine inverter installs, the DC bus continuous current this calculator emits is the input to the OCPD sizing rule — not the AC continuous rating. Banks larger than 500 Ah additionally need per-battery protection under E-11 (2025).
  • IEEE 1547-2018
    Grid-interactive inverters (when used in hybrid systems with utility tie-in) must respond to anti-islanding, voltage and frequency ride-through within bounds defined per Category I/II/III response.
    Why it matters: Stand-alone inverter sizing (this tool) does not require IEEE 1547 compliance; if your design becomes grid-interactive, the inverter SKU you pick must carry an IEEE 1547-2018 certification on its nameplate.

Citations are paraphrased for brevity. Always work from the most recent published edition of each standard for permit submittals.